Analysis of Losses Due to Load Unbalance in a 2000 kVA Transformer at Supermall Mansion 2 Tower Tanglin Surabaya

Authors

  • Reza Sarwo Widagdo Universitas 17 Agustus 1945 Surabaya
  • Aris Heri Andriawan Department of Electrical Engineering, Universitas 17 Agustus 1945 Surabaya

DOI:

https://doi.org/10.23960/jesr.v5i2.144

Keywords:

Load Unbalanced, Transformer Loading, Transformer Losses

Abstract

The load unbalance causes a neutral current, the current flowing in the neutral conductor will cause an increase in losses in the transformer. The greater the losses incurred, the efficiency and reliability of the transformer will decrease. Based on this, a study was conducted on analyzing the losses on distribution transformers at Supermall Mansion 2 Tower Tanglin which aims to determine the percentage value of transformer loading, the value of transformer imbalance, the value of transformer losses, and the value of transformer efficiency. This is done so that the value of the installed transformer does not exceed the applicable SPLN value. During the measurement, it was found that the percentage value of the transformer loading was 38.88% during the daytime and 48.89% at night (maximum SPLN 80%, minimum 40%). The load unbalance value is 11.66% during the daytime and 10.33% at night (SPLN is categorized as good if < 10%). Copper losses (Pcu) are 91.3 kW during the daytime and 94.2 kW at night. The value of losses due to neutral currents is 0.134 kW with a percentage of 0.0071% during the daytime and 0.173 kW with a percentage of 0.0090% at night. The percentage of the current value in the neutral conductor is 26.36% during the day and 24.04% at night (SPLN is categorized as good if < 20%).

Downloads

Download data is not yet available.

Author Biography

Aris Heri Andriawan, Department of Electrical Engineering, Universitas 17 Agustus 1945 Surabaya

Department of Electrical Engineering, Faculty of Engineering, Universitas 17 Agustus 1945 Surabaya

References

Ma, K., Fang, L., & Kong, W. (2020). Review of distribution network phase unbalance: Scale, causes, consequences, solutions, and future research directions. CSEE Journal of Power and Energy systems, 6(3), 479-488.

Fidalgo, J. N., Moreira, C., & Cavalheiro, R. (2019, June). Impact of load unbalance on low voltage network losses. In 2019 IEEE Milan PowerTech (pp. 1-5). IEEE.

Naumov, I., Podyachikh, S., Ivanov, D., Tretyakov, A., & Bastron, A. (2021). Analysis of unbalanced load low-voltage electrical networks operating modes. In E3S Web of Conferences (Vol. 295, p. 02005). EDP Sciences.

Ciontea, C. I., & Iov, F. (2021). A study of load imbalance influence on power quality assessment for distribution networks. Electricity, 2(1), 77-90.

Sahito, A. A., Memon, Z. A., Shaikh, P. H., Rajper, A. A., & Memon, S. A. (2015). Unbalanced loading; An overlooked contributor to power losses in HESCO. Sindh University Research Journal-SURJ (Science Series), 47(4).

Salustiano, R., Neto, E., & Martinez, M. (2013, June). The unbalanced load cost on transformer losses at a distribution system. In 22nd International Conference and Exhibition on Electricity Distribution (CIRED 2013) (pp. 1-3). IET.

Dong, Y., & Shi, Y. (2021). Analysis of Losses in Cables and Transformers with Unbalanced Load and Current Harmonics. Journal of Electrical and Electronic Engineering, 9(3), 78-86.

Rinas, I., Suartika, I., & Pemayun, A. (2018). Analysis of the Increase of Transformer Power Losses due to the Operation of Unbalanced Nonlinier Loads. Journal of Electrical, Electronics and Informatics, 2(38), 10-24843.

Bantras, T., ?uk, V., Cobben, J. F. G., & Kling, W. L. (2012, July). Estimation and classification of power losses due to reduced power quality. In 2012 IEEE Power and Energy Society General Meeting (pp. 1-6). IEEE.

Pajic, S., & Emanuel, A. E. (2009). Effect of neutral path power losses on the apparent power definitions: A preliminary study. IEEE transactions on Power Delivery, 24(2), 517-523.

Pan, B., Zhang, Y., Gui, X., Wan, Y., & Wang, G. (2019, April). Analysis and Research of Three-phase Unbalance in Distribution Transformers. In IOP Conference Series: Earth and Environmental Science (Vol. 252, No. 3, p. 032196). IOP Publishing.

Gupta, N., Swarnkar, A., & Niazi, K. R. (2011, July). A novel strategy for phase balancing in three-phase four-wire distribution systems. In 2011 IEEE Power and Energy Society General Meeting (pp. 1-7). IEEE.

Ali, B., Khan, A. A., & Siddique, I. (2018, December). Analysis of distribution system losses due to harmonics in IESCO. In 2018 IEEE International Conference on Information and Automation for Sustainability (ICIAfS) (pp. 1-6). IEEE.

Downloads

Published

2023-12-31

How to Cite

[1]
Reza Sarwo Widagdo and Aris Heri Andriawan, “Analysis of Losses Due to Load Unbalance in a 2000 kVA Transformer at Supermall Mansion 2 Tower Tanglin Surabaya”, gas, vol. 5, no. 2, pp. 78–84, Dec. 2023.

Issue

Section

Articles